Charging the Lead Acid Battery

written by: Olga Mledenova; article published: year 2007, month 01;

In: Root » Electronics and communication » Batteries

  Share  
|
  PL  |  NL  |  FR  |  ES  |  PT  |  IT  |  DE  |  DK  |  NO  |  SE  |  FI  |  GR  |  JP  |  CN  |  KR  |  RU  |  AE


The charge algorithm for lead acid batteries differs from nickel-based chemistry in that voltage limiting rather than current limiting is used. Charge time of a sealed lead acid (SLA) is 12 to 16 hours. With higher charge currents and multi-stage charge methods, charge time can be reduced to 10 hours or less. SLAs cannot be fully charged as quickly as nickel-based systems. A multi-stage charger applies constant-current charge, topping charge and float charge. During the constant current charge, the battery charges to 70 percent in about five hours; the remaining 30 percent is completed by the slow topping charge. The topping charge lasts another five hours and is essential for the well-being of the battery. This can be compared to a little rest after a good meal before resuming work. If the battery is not completely saturated, the SLA will eventually lose its ability to accept a full charge and the performance of the battery is reduced. The third stage is the float charge, which compensates for the self-discharge after the battery has been fully charged.

Correctly setting the cell-voltage limit is critical. A typical voltage limit is from 2.30V to 2.45V. If a slow charge is acceptable, or the room temperature may exceed 30°C (86°F), the recommended voltage limit is 2.35V/cell. If a faster charge is required, and the room temperature will remain below 30°C, 2.40 to 2.45V/cell may be used.

The charge voltage limit is a momentary voltage peak and the battery cannot dwell on that level. This voltage crest is only used when applying a full charge cycle to a battery that has been discharged. Once fully charged and at operational readiness, a float charge is applied, which is held constant at a lower voltage level. The recommended float charge voltage of most low-pressure lead acid batteries is between 2.25 to 2.30V/cell. A good compromise is 2.27V.

The optimal float charge voltage shifts with temperature. A higher temperature demands slightly lower voltages and a lower temperature demands higher voltages. Chargers that are exposed to large temperature fluctuations are equipped with temperature sensors to optimize the float voltage.

Regardless of how well the float voltage may be compensated, there is always a compromise. The author of a paper in a battery seminar explained that charging a sealed lead acid battery using the traditional float charge techniques is like 'dancing on the head of a pin'. The battery wants to be fully charged to avoid sulfation on the negative plate, but does not want to be over-saturated which causes grid corrosion on the positive plate. In addition to grid corrosion, too high a float charge contributes to loss of electrolyte.

Differences in the aging of the cells create another challenge in finding the optimum float charge voltage. With the development of air pockets within the cells over time, some batteries exhibit hydrogen evolution from overcharging. Others undergo oxygen recombination in an almost starved state. Since the cells are connected in series, controlling the individual cell voltages during charge is virtually impossible. If the applied cell voltage is too high or too low for a given cell, the weaker cell deteriorates further and its condition becomes more pronounced with time. Companies have developed cell-balancing devices that correct some of these problems but these devices can only be applied if access to individual cells is possible.

A ripple voltage imposed on the charge voltage also causes problems for lead acid batteries, especially the larger VRLA. The peak of the ripple voltage constitutes an overcharge, causing hydrogen evolution; the valleys induce a brief discharge causing a starved state. Electrolyte depletion may be the result.

Much has been said about pulse charging lead acid batteries. Although there are obvious benefits of reduced cell corrosion, manufacturers and service technicians are not in agreement regarding the benefit of such a charge method. Some advantages are apparent if pulse charging is applied correctly, but the results are non-conclusive. Whereas the voltage settings apply to low-pressure lead acid batteries with a pressure relief valve setting of about 34 kPa (5 psi), the cylindrical SLA by Hawker requires higher voltage settings. These voltage limits should be set according to the manufacturer’s specifications. Failing to apply the recommended voltage threshold for these batteries causes a gradual decrease in capacity due to sulfation. Typically, the Hawker cell has a pressure relief setting of 345 kPa (50 psi). This allows some recombination of the gases during charge. An SLA must be stored in a charged state. A topping charge should be applied every six months to avoid the voltage from dropping below 2.10V/cell. The topping charge requirements may differ with cell manufacturers. Always follow the time intervals recommended by the manufacturer.

By measuring the open cell voltage while in storage, an approximate charge-level indication can be obtained. A voltage of 2.11V, if measured at room temperature, reveals that the cell has a charge of 50 percent and higher. If the voltage is at or above this threshold, the battery is in good condition and only needs a full charge cycle prior to use. If the voltage drops below 2.10V, several discharge/charge cycles may be required to bring the battery to full performance. When measuring the terminal voltage of any cell, the storage temperature should be observed. A cool battery raises the voltage slightly and a warm one lowers it.

Plastic SLA batteries arriving from vendors with less than 2.10V per cell are rejected by some buyers who inspect the battery during quality control. Low voltage suggests that the battery may have a soft short, a defect that cannot be corrected with cycling. Although cycling may increase the capacity of these batteries, the extra cycles compromise the service life of the battery. Furthermore, the time and equipment required to make the battery fully functional adds to operational costs.

The Hawker cell can be stored at voltages as low as 1.81V. However, when reactivating the cells, a higher than normal charge voltage may be required to convert the large sulfite crystals back to good active material.

Caution: When charging a lead acid battery with over-voltage, current limiting must be applied once the battery starts to draw full current. Always set the current limit to the lowest practical setting and observe the battery voltage and temperature during the procedure. If the battery does not accept a normal charge after 24 hours under elevated voltage, a return to normal condition is unlikely.

The price of the Hawker cell is slightly higher than that of the plastic equivalent, but lower than the NiCd. Also known as the ‘Cyclone’, this cell is wound similar to a cylindrical NiCd. This construction improves the cell’s stability and provides higher discharge currents when compared to the flat plate SLA. Because of its relatively low self-discharge, Hawker cells are well suited for defibrillators that are used on standby mode.

Lead acid batteries are preferred for UPS systems. During prolonged float charge, a periodic topping charge, also known as an ‘equalizing charge’, is recommended to fully charge the plates and prevent sulfation. An equalizing charge raises the battery voltage for several hours to a voltage level above that specified by the manufacturer. Loss of electrolyte through elevated temperature may occur if the equalizing charge is not administered correctly. Because no liquid can be added to the SLA and VRLA systems, a reduction of the electrolyte will cause irreversible damage. Manufacturers and service personnel are often divided on the benefit of the equalizing charge.

Some exercise, or brief periodic discharge, is believed to prolong battery life of lead acid systems. If applied once a month as part of an exercising program, the depth of discharge should only be about 10 percent of its total capacity. A full discharge as part of regular maintenance is not recommended because each deep discharge cycle robs service life from the battery.

More experiments are needed to verify the benefit of exercising lead acid batteries. Again, manufacturers and service technicians express different views on how preventive maintenance should be carried out. Some experts prefer a topping charge while others recommend scheduled discharges. No scientific data is available on the benefit of frequent shallow discharges as opposed to fewer deep discharges or discharge pulses.

Disconnecting the float charge while the VRLA is on standby is another method of prolonging battery life. From time-to-time, a topping charge is applied to replenish the energy lost through self-discharge. This is said to lower cell corrosion and prolong battery life. In essence, the battery is kept as if it was in storage. This only works for applications that do not draw a load current during standby. In many applications, the battery acts as an energy buffer and needs to be under continuous charge.

Important: In case of rupture, leaking electrolyte or any other cause of exposure to the electrolyte, flush with water immediately. If eye exposure occurs, flush with water for 15 minutes and consult a physician immediately.

Share

Disclaimer

1) E-articles is not responsible for the information contained by this article as well for any and all copyright infringements by authors and writers. E-articles is a free information resource. If you suspect this article for any copyright infringement, please read the terms of service and contact us or use the "Report this article" button on this page to investigate the problem.